- Product description
-
Product descriptionCoaxial data cable protection devices
• High pulsed current carrying capacity 2 x 2.5 kA (10/350)
• Simple mounting (adapter plug), m = plug/f = female connector
• Optimised transmission behaviour
• 5-year guarantee
• With N connector
• Including OBO M25 Quick clip for simple installation
- Technical data
-
Technical data
Arrestor monitoring no Cable type for surge protection devices Data cable COAX Capacity (wire-earth) <20 pF Capacity (wire-wire) <10 pF Cut-off frequency 3000 MHz Dimension 130V Explosion-tested version no Impulse durability wire-earth C2: 10 kV / 5 kA (8/20µs) Impulse durability wire-wire C2: 10 kV / 5 kA (8/20µs) Insertion loss ≤0,62 dB Insulation resistance >1 GΩ Kategorie Type 1+2 / D1+C2 Lightning impulse current 2,5 kA Lightning protection zone LPZ 0→2 Maximum continuous voltage AC 130 V Maximum continuous voltage DC 185 V Nominal load current AC 7 A Nominal load current DC 10 A Number of poles 1 Permitted temperature range, max. 80 °C Permitted temperature range, min. -40 °C Plug-in system N Protection level <800 V Protection level wire-earth <800 V Protection level wire-wire <800 V Protection rating IP40 Return loss ≥14 dB Screening Direct Shielding connection available yes Signalling on device None SPD to IEC 61643-21 Class I+II / D1+C2 Telecommunications contact no Testing standard IEC 61643-21 Total discharge current (10/350) 5 kA Total discharge current (8/20) 10 kA Wave resistance 50 Ω - All types
- Downloads
-
Data sheet DS-N W/W / 5093988 , 0.19MB , pdfTechnical information Technical information, DS-N , 0.06MB , pdfTechnical information Technical information, DS-N...; DS-BNC...; DS-TNC...; DS-F... , 0.06MB , pdf
Ukraine - English